Ambient temperature : 30ºC
Conductor operating temperature : 70ºC
CURRENT CARRYING CAPACITY (AMPS) |
||||||
Conductor Cross Sectional Area |
Enclosed in an insulated wall | Enclosed in conduit on a wall or in trunking etc... | Clipped direct | |||
1.0mm² | 11A | 10A | 13A | 11.5A | 15A | 13.5A |
1.5mm² | 14A | 13A | 16.5A | 15A | 19.5A | 17.5A |
2.5mm² | 18.5A | 17.5A | 23A | 20A | 27A | 24A |
4.0mm² | 25A | 23A | 30A | 27A | 36A | 32A |
6.0mm² | 32A | 29A | 38A | 34A | 46A | 41A |
10.0mm² | 43A | 39A | 52A | 46A | 63A | 57A |
16.0mm² | 57A | 52A | 69A | 62A | 85A | 76A |
VOLTAGE DROP (PER AMPERE MTRE) | |||
Conductor Cross Sectional Area | Two Core d.c. | Two Core
Cable single phase a.c. |
Three or Four
core cable three phase a.c. |
1.0mm² | 44mV | 44mV | 38mV |
1.5mm² | 29mV | 29mV | 25mV |
2.5mm² | 18mV | 18mV | 15mV |
4.0mm² | 11mV | 11mV | 9.5mV |
6.0mm² | 7.3mV | 7.3mV | 6.4mV |
10.0mm² | 4.4mV | 4.4mV | 3.8mV |
16.0mm² | 2.8mV | 2.8mV | 2.4mV |
If cables are to be used in ambient air temperature other than 30ºC the following ratings should be applied. | |||||||||
Ambient air temperature 30ºC | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 |
Rating Factor | 1.03 | 1.0 | 0.94 | 0.87 | 0.79 | 0.71 | 0.61 | 0.50 | 0.35 |
CURRENT CARRYING CAPACITY (AMPS) |
||||||||
Clipped Direct | In Free Air | Direct in Ground or Ducting | ||||||
Nominal Conductor Area | 2 Core | 3 & 4 Core | Nominal Conductor Area | 2 Core | 3 & 4 Core | Nominal Conductor Area | 2 Core | 3 & 4 Core |
1.5mm² | 27 | 23 | 1.5mm² | 29 | 25 | 1.5mm² | 25 | 21 |
2.5mm² | 36 | 31 | 2.5mm² | 39 | 33 | 2.5mm² | 33 | 28 |
4.0mm² | 49 | 42 | 4.0mm² | 52 | 44 | 4.0mm² | 43 | 36 |
6.0mm² | 62 | 53 | 6.0mm² | 66 | 56 | 6.0mm² | 53 | 44 |
10.0mm² | 85 | 73 | 10.0mm² | 90 | 78 | 10.0mm² | 71 | 58 |
16.0mm² | 110 | 94 | 16.0mm² | 115 | 99 | 16.0mm² | 91 | 75 |
25.0mm² | 146 | 124 | 25.0mm² | 152 | 131 | 25.0mm² | 116 | 96 |
35.0mm² | 180 | 154 | 35.0mm² | 188 | 162 | 35.0mm² | 139 | 115 |
50.0mm² | 219 | 187 | 50.0mm² | 228 | 197 | 50.0mm² | 164 | 135 |
70.0mm² | 279 | 238 | 70.0mm² | 291 | 251 | 70.0mm² | 203 | 167 |
95.0mm² | 338 | 289 | 95.0mm² | 354 | 304 | 95.0mm² | 239 | 197 |
120.0mm² | 392 | 335 | 120.0mm² | 410 | 353 | 120.0mm² | 271 | 223 |
150.0mm² | 451 | 386 | 150.0mm² | 472 | 406 | 150.0mm² | 306 | 251 |
185.0mm² | 515 | 441 | 185.0mm² | 539 | 463 | 185.0mm² | 343 | 281 |
240.0mm² | 607 | 520 | 240.0mm² | 636 | 546 | 240.0mm² | 395 | 324 |
300.0mm² | 698 | 599 | 300.0mm² | 732 | 628 | 300.0mm² | 446 | 365 |
400.0mm² | 787 | 673 | 400.0mm² | 847 | 728 | 400.0mm² | - | - |
For 2 core - single phase a.c., 3 & 4 core - three phase a.c. - ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.
For cables of 5 cores and above it is assumed only 2 cores are loaded simultaneously (ie live and neutral) and the 2 core rating should be taken. In instances where several cores are loaded simultaneously, the following rating factors should be applied to the 2 core current rating.
Number of cores | 2 | 3 | 4 | 5 | 6 | 7 | 10 | 12 | - |
Factor | 1.0 | 0.87 | 0.78 | 0.72 | 0.67 | 0.63 | 0.56 | 0.53 | - |
Number of cores | 14 | 19 | 24 | 27 | 30 | 37 | 44 | 46 | 48 |
Factor | 0.51 | 0.45 | 0.42 | 0.40 | 0.39 | 0.36 | 0.34 | 0.33 | 0.33 |
If cables laid in air temperatures other than those specified the following ratings should be applied: | |||||||
Ambient air temperature 30ºC | 25 | 30 | 35 | 40 | 45 | 50 | 55 |
Rating Factor | 1.0 | 0.96 | 0.92 | 0.88 | 0.83 | 0.78 | 0.73 |
If cables laid in ground and single way ducts with temperatures other than those specified the following ratings should be applied: | |||||||
Ambient air temperature 30ºC | 10 | 15 | 20 | 25 | 30 | 35 | 40 |
Rating Factor | 1.03 | 1.0 | 0.97 | 0.93 | 0.89 | 0.86 | 0.82 |
VOLTAGE DROPS (AMPS PER METRE) | |||||||
Conductor Cross Sectional Area | Two Core
Cable d.c. |
Two
Core Cable Single Phase a.c. |
Three
or Four Cable Three Phase a.c. |
||||
1.5mm² | 31mV | 31mV | 27mV | ||||
2.5mm² | 19mV | 19mV | 16mV | ||||
4.0mm² | 12mV | 12mV | 10mV | ||||
6.0mm² | 7.9mV | 7.9mV | 6.8mV | ||||
10.0mm² | 4.7mV | 4.7mV | 4.0mV | ||||
16.0mm² | 2.9mV | 2.9mV | 2.5mV | ||||
r | x | z | r | x | z | ||
25.0mm² | 1.85mV | 1.85mV | 0.160mV | 1.90mV | 1.60mV | 0.140mV | 1.65mV |
35.0mm² | 1.35mV | 1.35mV | 0.155mV | 1.35mV | 1.15mV | 0.135mV | 1.15mV |
50.0mm² | 0.98mV | 0.99mV | 0.155mV | 1.00mV | 0.86mV | 0.135mV | 0.87mV |
70.0mm² | 0.67mV | 0.67mV | 0.150mV | 0.69mV | 0.59mV | 0.130mV | 0.60mV |
95.0mm² | 0.49mV | 0.50mV | 0.150mV | 0.52mV | 0.43mV | 0.130mV | 0.45mV |
120.0mm² | 0.39mV | 0.40mV | 0.145mV | 0.42mV | 0.34mV | 0.130mV | 0.37mV |
150.0mm² | 0.31mV | 0.32mV | 0.145mV | 0.35mV | 0.28mV | 0.125mV | 0.30mV |
185.0mm² | 0.25mV | 0.26mV | 0.145mV | 0.29mV | 0.22mV | 0.125mV | 0.26mV |
240.0mm² | 0.195mV | 0.20mV | 0.140mV | 0.24mV | 0.175mV | 0.125mV | 0.21mV |
300.0mm² | 0.155mV | 0.16mV | 0.140mV | 0.21mV | 0.140mV | 0.120mV | 0.185mV |
400.0mm² | 0.120mV | 0.13mV | 0.145mV | 0.195mV | 0.115mV | 0.125mV | 0.170mV |