Technical Information for :
Flat Twin & Earth BS6004
Flat Three Core & Earth BS6004
Ambient temperature : 30ºC
Conductor operating temperature : 70ºC
CURRENT-CARRYING CAPACITY (AMPS) | ||||||
| Conductor cross sectional area | enclosed in an insulated wall | enclosed in conduit on a wall or in trunking etc. | clipped direct | |||
| 1.0mm² | 11A | 10A | 13A | 11.5A | 15A | 13.5A |
| 1.5mm² | 14A | 13A | 16.5A | 15A | 19.5A | 17.5A |
| 2.5mm² | 18.5A | 17.5A | 23A | 20A | 27A | 24A |
| 4.0mm² | 25A | 23A | 30A | 27A | 36A | 32A |
| 6.0mm² | 32A | 29A | 38A | 34A | 46A | 41A |
| 10.0mm² | 43A | 39A | 52A | 46A | 63A | 57A |
| 16.0mm² | 57A | 52A | 69A | 62A | 85A | 76A |
| VOLTAGE DROP (PER AMPERE PER METRE) | |||
| Conductor cross sectional area | Two-core d.c. | Two-core cable single phase a.c. | Three or four core cable three phase a.c. |
| 1.0mm² | 44mV | 44mV | 38mV |
| 1.5mm² | 29mV | 29mV | 25mV |
| 2.5mm² | 18mV | 18mV | 15mV |
| 4.0mm | 11V | 11mV | 9.5mV |
| 6.0mm² | 7.3mV | 7.3mV | 6.4mV |
| 10.0mm² | 4.4mV | 4.4mV | 3.8mV |
| 16.0mm² | 2.8mV | 2.8mV | 2.4mV |
If cables are to be used in ambient air temperature other than 30ºC the following rating factors should be applied | |||||||||
| Ambient air temperature °C | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 |
| Rating Factor | 1.03 | 1.0 | 0.94 | 0.87 | 0.79 | 0.71 | 0.61 | 0.50 | 0.35 |
XLPE/PVC/SWA/PVC ARMOURED CABLE
| CURRENT CARRYING CAPACITY (AMPS) | ||||||||
| Direct Burial | In Single-Way Duct | Air | ||||||
| Nominal conductor area | 2 Core | 3 & 4 Core | Nominal conductor area | 2 Core | 3 & 4 Core | Nominal conductor area | 2 Core | 3 & 4 Core |
| 1.5mm² | 38 | 32 | 1.5mm² | 31 | 26 | 1.5mm² | 31 | 26 |
| 2.5mm² | 49 | 42 | 2.5mm² | 41 | 34 | 2.5mm² | 41 | 35 |
| 4.0mm² | 65 | 55 | 4.0mm² | 53 | 45 | 4.0mm² | 55 | 47 |
| 6.0mm² | 81 | 69 | 6.0mm² | 67 | 56 | 6.0mm² | 70 | 59 |
| 10.0mm² | 109 | 92 | 10.0mm² | 89 | 75 | 10.0mm² | 95 | 82 |
| 16.0mm² | 141 | 119 | 16.0mm² | 115 | 96 | 16.0mm² | 126 | 107 |
| 25.0mm² | 183 | 152 | 25.0mm² | 148 | 124 | 25.0mm² | 164 | 140 |
| 35.0mm² | 219 | 182 | 35.0mm² | 178 | 149 | 35.0mm² | 202 | 172 |
| 50.0mm² | 259 | 217 | 50.0mm² | 211 | 177 | 50.0mm² | 244 | 209 |
| 70.0mm² | 317 | 266 | 70.0mm² | 260 | 218 | 70.0mm² | 306 | 263 |
| 95.0mm² | 381 | 319 | 95.0mm² | 313 | 263 | 95.0mm² | 378 | 324 |
| 120.0mm² | 433 | 363 | 120.0mm² | 357 | 300 | 120.0mm² | 437 | 376 |
| 150.0mm² | 485 | 406 | 150.0mm² | 401 | 338 | 150.0mm² | 499 | 430 |
| 185.0mm² | 547 | 458 | 185.0mm² | 455 | 382 | 185.0mm² | 576 | 495 |
| 240.0mm² | 632 | 529 | 240.0mm² | 527 | 442 | 240.0mm² | 680 | 584 |
| 300.00mm² | 708 | 592 | 300.00mm² | 592 | 496 | 300.00mm² | 775 | 666 |
| 400.00mm² | 799 | 667 | 400.00mm² | 669 | 570 | 400.00mm² | 892 | 766 |
Standard depth of laying 0.5m
Thermal resistivity of soil 1.2°C m/W
Standard ground temperature 15°C
Ambient air temperature 25°C
Maximum conductor temperature 90°C
For 2 core - single phase a.c., 3 & 4 core - three phase a.c. ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.
For cables of 5 cores and above it is assumed only 2 cores are loaded simultaneously (ie live and neutral) and the 2 core rating should be taken. In instances where several cores are loaded simultaneously, the following rating factors should be applied to the 2 core current rating:
| Number of cores | 2 | 3 | 4 | 5 | 6 | 7 | 10 | 12 | - |
| Factor | 1.0 | 0.87 | 0.78 | 0.72 | 0.67 | 0.63 | 0.56 | 0.53 | - |
| Number of cores | 14 | 19 | 24 | 27 | 30 | 37 | 44 | 46 | 48 |
| Factor | 0.51 | 0.45 | 0.42 | 0.40 | 0.39 | 0.36 | 0.34 | 0.33 | 0.33 |
For cables laid in air temperatures other than those specified the following rating factors should be applied:
| Ambient air temp ºC | 25 | 30 | 35 | 40 | 45 | 50 | 55 |
| Rating Factor | 1.0 | 0.96 | 0.92 | 0.88 | 0.83 | 0.78 | 0.73 |
For cables laid in ground and single way ducts with temperatures other than those specified the following rating factors should be applied:
| Ambient air temp ºC | 10 | 15 | 20 | 25 | 30 | 35 | 40 |
| Rating Factor | 1.03 | 1.0 | 0.97 | 0.93 | 0.89 | 0.86 | 0.82 |
VOLTAGE DROP (AMPS PER METRE) | |||||||
| Conductor cross sectional area | Two core cable d.c. | Two core cable single phase a.c. | Three or four core cable three phase a.c. | ||||
| 1.5mm² | 31mV | 31mV | 27mV | ||||
| 2.5mm² | 19mV | 19mV | 16mV | ||||
| 4.0mm² | 12mV | 12mV | 10mV | ||||
| 6.0mm² | 7.9mV | 7.9mV | 6.8mV | ||||
| 10.0mm² | 4.7mV | 4.7mV | 4.0mV | ||||
| 16.0mm² | 2.9mV | 2.9mV | 2.5mV | ||||
| r | x | z | r | x | z | ||
| 25.0mm² | 1.85mV | 1.85mV | 0.160mV | 1.90mV | 1.60mV | 0.140mV | 1.65mV |
| 35.0mm² | 1.35mV | 1.35mV | 0.155mV | 1.35mV | 1.15mV | 0.135mV | 1.15mV |
| 50.0mm² | 0.98mV | 0.99mV | 0.155mV | 1.00mV | 0.86mV | 0.135mV | 0.87mV |
| 70.0mm² | 0.67mV | 0.67mV | 0.150mV | 0.69mV | 0.59mV | 0.130mV | 0.60mV |
| 95.0mm² | 0.49mV | 0.50mV | 0.150mV | 0.52mV | 0.43mV | 0.130mV | 0.45mV |
| 120.0mm² | 0.39mV | 0.40mV | 0.145mV | 0.42mV | 0.34mV | 0.130mV | 0.37mV |
| 150.0mm² | 0.31mV | 0.32mV | 0.145mV | 0.35mV | 0.28mV | 0.125mV | 0.30mV |
| 185.0mm² | 0.25mV | 0.26mV | 0.145mV | 0.29mV | 0.22mV | 0.125mV | 0.26mV |
| 240.0mm² | 0.195mV | 0.20mV | 0.140mV | 0.24mV | 0.175mV | 0.125mV | 0.21mV |
| 300.0mm² | 0.155mV | 0.16mV | 0.140mV | 0.21mV | 0.140mV | 0.120mV | 0.185mV |
| 400.0mm² | 0.120mV | 0.13mV | 0.145mV | 0.195mV | 0.115mV | 0.125mV | 0.170mV |